PXe-C Series Three Phase Static Frequency Converters | SFC
PXe-330000-C Series
PX Electronics PXe-C Series Three-Phase Static Frequency Converters provide controlled voltage and frequency conversion for commercial, industrial and specialist electrical systems requiring a stable three-phase AC supply. The PXe-330000-C Series offers stable, reliable 50Hz to 60Hz and 60Hz to 50Hz power conversion for industrial equipment, shipping and marine systems, export testing, and manufacturing environments. Designed for continuous-duty operation, the PXe-330000-C series delivers stable three-phase output and protection for all types of machinery from rotating motors to specialist electrical loads.
Using solid-state IGBT PWM conversion technology, each system converts incoming AC power to DC, then generates a controlled AC output at the required power frequency. This makes the PXe-330000-C range suitable for equipment operating across different global power standards, including imported machinery, export production testing and industrial sites requiring dependable frequency conversion.
Technical Highlights for Three Phase Frequency Conversion
50Hz and 60Hz Frequency Conversion
PX static frequency converters can be configured for 50Hz or 60Hz input supplies and provide a regulated 50Hz or 60Hz output. Typical systems can accommodate a 47-63Hz input range, allowing 50Hz to 60Hz, 60Hz to 50Hz, 50Hz to 50Hz and 60Hz to 60Hz applications, with voltage conversion, galvanic isolation and regulation incorporated where required.
Soft-Start Capability
Controlled soft-start operation progressively applies the output supply, helping to reduce load inrush current, limit mechanical stress and provide a more controlled start for motors, compressors and other demanding loads.
Line voltage drop compensation
Provides adjustment for voltage drop across three-phase output cabling, helping maintain the specified operating voltage at the connected load, particularly on higher-power installations and longer cable runs.
Industrial Load Support
Suitable for resistive, inductive, and unbalanced loads, including motors, pumps, compressors, HVAC equipment, and production machinery.
Precise Output Control
Provides precise control of output voltage, current and frequency, maintaining a stable three-phase supply across varying load conditions.
IGBT PWM Conversion with Harmonic Mitigation
Solid-state IGBT PWM technology provides stable voltage and frequency conversion. Optional 12-pulse and 18-pulse rectifier arrangements improve the input current waveform, bringing it closer to a sine wave while significantly reducing dominant lower-order harmonics and improving supply-side power quality.
Transformer Isolation, Continuous Duty & Monitoring
Integrated transformer isolation provides electrical separation between the incoming supply and connected equipment. The PXe-C Series is designed for continuous operation and can be supplied with front-panel control, HMI, remote interfaces, communications and optional independent watchdog monitoring.
Product Information
PXe-C Series System Configuration
PXe-C Series Three-Phase Static Frequency Converters provide controlled voltage and frequency conversion for commercial, industrial and specialist electrical systems. Converters can be specified with three-phase input and either three-phase or single-phase output, according to the connected equipment.
The range supports 50Hz to 60Hz, 60Hz to 50Hz and selected 400Hz conversion duties, together with applications requiring voltage conversion, galvanic isolation or output regulation. Input and output voltages, frequencies and phase arrangements are selected around the available supply and load requirements.
PXe-C Series systems are available across a broad range of capacities, extending to 500kVA for suitable configurations. Smaller converters can support laboratory and production test equipment, while higher-capacity systems can be configured for industrial machinery, commercial installations and specialist electrical loads.
Solid-state IGBT PWM conversion provides a regulated sine-wave output, with integrated transformer isolation. Front-panel monitoring allows operators to check operating values and system status, while suitable communications interfaces can be specified for remote operation and integration.
Installation arrangements include compact, floor-standing and mobile configurations according to capacity and application. Standard enclosure protection is IP20, with IP21, IP22 and IP54 options available subject to the selected model and installation requirements.
Popular Configurations
The following examples illustrate typical three-phase voltage and frequency conversion applications. Other capacities, input supplies and output arrangements can be specified to meet customer requirements.
| MODEL | CAPACITY | INPUT | OUTPUT |
|---|---|---|---|
| PXe-330003-C | 3kVA | 380V L-L ±10% 50Hz Three Phase |
0–260V / 0–520V Adjustable 60Hz Three Phase |
| PXe-310006-C | 6kVA | 415V L-L ±10% 50Hz Three Phase |
115V 60Hz Single Phase |
| PXe-330010-C | 10kVA | 400V L-L ±10% 50Hz Three Phase |
0–260V / 0–520V Adjustable 50Hz / 60Hz Three Phase |
| PXe-330015-C | 15kVA | 400V L-L ±10% 50Hz Three Phase |
230V L-N / 400V L-L 60Hz Three Phase |
| PXe-330030-C | 30kVA | 415V L-L ±15% 50Hz Three Phase |
115V L-N / 200V L-L 60Hz Three Phase |
| PXe-330045-C | 45kVA | 400V L-L ±10% 50Hz Three Phase |
115V L-N / 200V L-L 60Hz Three Phase |
Configuration note: These examples illustrate possible electrical arrangements and are not fixed model specifications. Final voltage and frequency ratings, output current, load capability and protection requirements are confirmed for each application. Representative dimensions and weights are provided under Ordering & Options only for models supported by the current supplier mechanical schedule.
Three-Phase Distribution and Output Configurations
PXe-C Series converters can supply common European, North American and specialist three-phase voltage systems. Three-phase output configurations may be specified with a neutral where required, while three-phase to single-phase conversion can be provided for suitable loads.
The required transformer winding arrangement, neutral provision, earthing and output protection must be established for the connected equipment and installation.
High-Leg Delta Output Configurations
PXe-C Series converters can be specified with a 240/120V three-phase, four-wire High-Leg Delta output for suitable North American industrial and commercial applications.
In a typical High-Leg Delta configuration, 240V is available between each pair of phases. Two phases provide approximately 120V to neutral, while the high leg measures approximately 208V to neutral. The high leg must not be used to supply 120V line-to-neutral loads.
The high-leg designation, neutral arrangement, transformer winding configuration and distribution of line-to-neutral loads must be specified according to the customer’s electrical system.
Installation and Control
Converters can be supplied in appropriately sized enclosures for fixed industrial installations or applications requiring mobile equipment. Enclosure size, mounting, cooling, electrical connections and maintenance access depend on the selected rating and site conditions.
Front-panel operation and monitoring are provided according to the configured controller. RS232C is the standard communications interface, with RS485, Ethernet and GPIB options available on suitable configurations.
For motors, compressors, transformers and other demanding loads, the specification must consider starting current, power factor, non-linear loading and operating duty in addition to continuous kVA.
Approximate Dimensions and Weights | Standard IP20 Enclosures
The following dimensions and weights are nominal values for representative standard configurations. Both three-phase output and single-phase output models are included.
| MODEL NUMBER | CAPACITY | DIMENSIONS W × D × H (mm) | WEIGHT |
|---|---|---|---|
| Three-Phase Input / Three-Phase Output | |||
| PXe-330006-C | 6kVA | 430 × 650 × 600 | 92 kg |
| PXe-33007.5-C | 7.5kVA | 430 × 650 × 600 | 101 kg |
| PXe-330010-C | 10kVA | 430 × 650 × 600 | 110 kg |
| PXe-330015-C | 15kVA | 550 × 700 × 800 | 153 kg |
| PXe-330020-C | 20kVA | 550 × 700 × 800 | 177 kg |
| PXe-330030-C | 30kVA | 550 × 900 × 1000 | 273 kg |
| PXe-330045-C | 45kVA | 550 × 1000 × 1300 | 355 kg |
| PXe-330060-C | 60kVA | 550 × 1000 × 1300 | 380 kg |
| PXe-330100-C | 100kVA | 1050 × 700 × 1450 | 590 kg |
| PXe-330150-C | 150kVA | 1250 × 880 × 1450 | 780 kg |
| Three-Phase Input / Single-Phase Output | |||
| PXe-310010-C | 10kVA | 430 × 550 × 630 | 95 kg |
| PXe-310015-C | 15kVA | 430 × 550 × 800 | 117 kg |
| PXe-310020-C | 20kVA | 430 × 550 × 800 | 145 kg |
| PXe-310030-C | 30kVA | 430 × 700 × 800 | 220 kg |
| PXe-310050-C | 50kVA | 600 × 700 × 1350 | 360 kg |
| PXe-310060-C | 60kVA | 600 × 700 × 1350 | 400 kg |
| PXe-310075-C | 75kVA | 700 × 700 × 1700 | 460 kg |
| PXe-310100-C | 100kVA | 700 × 700 × 1700 | 650 kg |
Approximate Dimensions and Weights | Optional IP54 Enclosures
| MODEL NUMBER | CAPACITY | DIMENSIONS W × D × H (mm) | WEIGHT |
|---|---|---|---|
| Three-Phase Input / Three-Phase Output | |||
| PXe-330006-C | 6kVA | 550 × 650 × 700 | 120 kg |
| PXe-33007.5-C | 7.5kVA | 550 × 650 × 700 | 150 kg |
| PXe-330010-C | 10kVA | 550 × 650 × 700 | 160 kg |
| PXe-330015-C | 15kVA | 600 × 800 × 1000 | 280 kg |
| PXe-330020-C | 20kVA | 600 × 1000 × 1282 | 290 kg |
| PXe-330030-C | 30kVA | 600 × 1000 × 1282 | 350 kg |
| PXe-330045-C | 45kVA | 1000 × 700 × 1552 | 437 kg |
| PXe-330060-C | 60kVA | 1000 × 700 × 1552 | 485 kg |
| PXe-330100-C | 100kVA | 1000 × 700 × 1552 | 630 kg |
| PXe-330150-C | 150kVA | 1300 × 800 × 1650 | 871 kg |
| Three-Phase Input / Single-Phase Output | |||
| PXe-310010-C | 10kVA | 550 × 550 × 730 | 137 kg |
| PXe-310015-C | 15kVA | 550 × 550 × 900 | 158 kg |
| PXe-310020-C | 20kVA | 550 × 550 × 900 | 175 kg |
| PXe-310030-C | 30kVA | 550 × 550 × 900 | 250 kg |
Note: Dimensions and weights are nominal and based on representative standard IP20 and optional IP54 configurations. Final values may vary depending on the specified voltage, operating frequency, transformer arrangement and optional equipment. Higher-capacity units and configurations not listed above are available upon request, with dimensions and weights provided at quotation stage.
PXe-C Series Order Codes
You can derive a product order code from the main ordering information using the structure below.
The generic PXe-C Series model references follow the formats PXe-330000-C for three-phase input and three-phase output, and PXe-310000-C for three-phase input and single-phase output. The first six digits identify the phase arrangement and converter capacity.
For example, a 30kVA converter with three-phase input and three-phase output would use the base model:
PXe-330030-C
The complete order code identifies the electrical configuration, rating, enclosure and control arrangement:
PXe-330030-C-[INPUT]-[OUTPUT]-[RATING]-[ENCLOSURE]-[CONTROL]
Example:
PXe-330030-C-[3P415V50]-[3P200V60N]-[30KVA]-[IP20]-[MC]
This would represent:
(PXe-330030-C) – PX Electronics C-Series Static Frequency Converter, 30kVA
(3P415V50) – Three-phase, 415V line-to-line, 50Hz input
(3P200V60N) – Three-phase, 200V line-to-line, 60Hz output with neutral, providing approximately 115V line-to-neutral
(30KVA) – 30kVA rated capacity
(IP20) – Standard IP20 enclosure
(MC) – Manual Control
For this illustrative configuration, the complete order code would therefore be:
PXe-330030-C-3P415V50-3P200V60N-30KVA-IP20-MC
| MODEL | INPUT | OUTPUT | CAPACITY | ENCLOSURE | INTERFACE |
|---|---|---|---|---|---|
| PXe-330030-C C-Series Static Frequency Converter |
3P415V50 3P = Three Phase 415V = Input Voltage 50 = 50Hz |
3P200V60N 3P = Three Phase 200V = L-L Voltage 60 = 60Hz N = Neutral |
30KVA 30kVA capacity |
IP20 Standard enclosure |
MC Manual Control |
The examples above illustrate the order-code structure. Alternative voltage, frequency, phase and enclosure configurations are defined according to the customer’s application. The final order code is confirmed as part of the agreed specification.
Additional Available Options
IP21, IP22 and IP54 Enclosures
IP20 is the standard enclosure rating. IP21, IP22 and IP54 protection levels are available as options, subject to the selected model, cooling arrangements and installation requirements. IP54 does not automatically establish suitability for outdoor, marine or corrosive environments; those conditions require separate assessment.
Voltage, Frequency and Phase Conversion
Converters can be configured for different three-phase input and output voltages, including 50Hz, 60Hz and selected specialist operating frequencies. Three-phase to single-phase conversion can also be specified. Final arrangements depend on the available input supply and connected load.
High-Leg Delta Output
A 240/120V three-phase, four-wire High-Leg Delta arrangement can be specified where required. Please provide the total three-phase load, individual line-to-neutral loads, expected load distribution, neutral and earthing requirements and any site-specific phase designation requirements.
Input Harmonic Mitigation
Optional 12-pulse and 18-pulse rectifier configurations can be considered for suitable three-phase converters where reduced input current harmonic distortion is required. The appropriate arrangement depends on the system rating and installation.
Conformal Coating
Additional coating of internal PCBs and selected electronic components can be specified where increased protection from humidity or potentially corrosive atmospheres is required.
19-inch Rack-Mount Construction
Available on suitable smaller models where integration into an existing equipment rack, laboratory system or production test installation is required. Rack capacity, mounting support and cooling provision must be considered.
Communications and Remote Control
RS232C is the standard communications interface. RS485, Ethernet and GPIB are available as options on suitable controller configurations. Required protocols and remote functions are confirmed when specifying the equipment.
Remote Watchdog Monitoring
Independent monitoring arrangements can be considered for suitable larger converters, typically above 50kVA. Fault notification, event logging, remote operation and restart functions depend on the specified monitoring equipment and control configuration.
Cables and Terminations
Input and output cable assemblies, industrial connectors, hard-wire terminations and customer-specific connection arrangements can be provided according to the converter rating and site requirements.
Mobile Base and Handling Options
Wheeled bases, castors and suitable handling arrangements can be provided where equipment must be moved between test areas, production lines or service facilities. The arrangement depends on weight, enclosure size and installation conditions.
External Energy Metering
External energy metering can be incorporated where the customer requires additional consumption monitoring, measurement of individual output branches or integration with a preferred metering and communications system.
Information Required for Quotation
Please provide the available input voltage, frequency and phase arrangement; required output voltage, frequency and phase arrangement; continuous load rating; and details of the connected equipment.
Where applicable, include starting or inrush current, load power factor, non-linear load characteristics, neutral and earthing arrangements, output protection, duty cycle, enclosure protection, installation space, communications and any special testing or documentation requirements.
PX Electronics will review the application and confirm the proposed electrical configuration, nominal dimensions and weights, installation requirements and final order code at quotation stage.
PXe-330000-C Specification
| Capacity | |
| Single Phase Output (Other options available on request) |
kVA Ratings: 0.5kVA, 1kVA, 3kVA, 5kVA, 10kVA, 15kVA, 20kVA, 30kVA, 50kVA, 60kVA, 75kVA, 100kVA, 150kVA, 200kVA |
| Three Phase Output (Other options available on request) |
kVA Ratings: 1kVA, 3kVA, 6kVA, 7.5kVA, 10kVA, 15kVA, 20kVA, 30kVA, 45kVA, 60kVA, 100kVA, 150kVA, 200kVA, 300kVA, 400kVA, 500kVA |
| Input | |
| Three Phase (Select One Individual Voltage) |
(L-N/L-L) 115V/200V, 120V/208V, 127V/220V, 220V/380V, 230V/400V, 240V/415V, 254V/440V, 277V/480V, 400V/690V (±10% std, other options available) 3 Phase 3 Wire or 3 Phase 4 Wire |
| Frequency | 50Hz/60Hz ±5%, 400Hz (Optional) |
| Power Factor | ≥ 0.8 (standard type) ≥ 0.9 (optional type, 12 or 18 pulse) |
| Output | |
| Single Phase (Select One Individual Voltage) |
Fixed: 110V, 115V, 120V, 127V, 220V, 230V, 240V, 400V Adjustable: 0~300V |
| Three Phase (Select Voltages required) |
Fixed: (L-N/L-L) 115V/200V, 120/208V, 127/220V, 220/380V, 230/400V, 240/415V, 254/440V, 277/480V, 400/690V, 3 Phase 3 Wire or 3 Phase 4 Wire Adjustable: Low range 0~260V/High range 0~520V, 3 Phase 3 Wire or 3 Phase 4 Wire Optional North American configuration: 240/120V, 3 Phase 4 Wire High-Leg Delta |
| Frequency | Fixed: 50Hz, 60Hz, 100Hz, 200Hz, 45-200Hz (adjustable) Optional: 400Hz, 40Hz~500Hz (adjustable), 16.67Hz, 25Hz, 50Hz, 60Hz, 400-1000Hz |
| Voltage Accuracy | ≤ ±1% FS |
| Frequency Accuracy | ≤ ±0.1% FS |
| Total Harmonic Distortion | THD ≤ 3% @ linear load, pure sine wave output |
| Load Current Crest Factor Capability | 3:1 |
| Overload Capacity | 100% continuous <110% – 15 minutes, <125- 10 minutes, <150%- 1 minute, <200%- 5 seconds >200% output cut off (other variations available upon request) |
| Interface | RS232C std, RS485, GPIB, Ethernet (Optional) |
| Protection | Over-current, over-voltage, over-power, over-temp, short circuit, alarm and indicators |
| Enclosure IP Rating | IP20 (Standard), IP21, IP22 & IP54 (Optional). Special enclosure options available |
| LCD Display | Frequency meter, Voltage meter, Current meter, Power Meter, PF meter |
| Connectors | Hard-wire terminals, EN60309, MIL-STD, or client choice |
| Operating conditions | |
| Temperature | Operation: -10℃~55℃ Ambient: -10℃~45℃ |
| Noise | ≤ 65dB at 1 meter EN 55022, IEC1000-4 |
| Humidity | 10~90% non-condensing |
| Cooling | Variable speed fan, filtered air intake in base, exhaust at rear |
| Altitude | ≤ 1800m |
| Castors or Feet | 0.5-3kVA have rubber feet and lifting handles, 4kVA+ have castors with front brakes. A/Vs or feet optional |
| Reliability and Efficiency | |
| Mean Time Between Failure (MTBF) | 50,000Hrs |
| Mean Time To Restore (MTTR) | < 30 min |
| Overall Efficiency | ≥ 85% |
| Standards | |
| CE, GB50054-95, GB 50150-1991, GB 50150-2006, GB 50171-1992, GB/T 16935.5-2008, GB/T16935.4-2011 | |
| EN IEC61000-3-2, EN 61000-3-3, EN55032, EN55035, MIL-STD-1399, MIL-STD 461, MIL-STD704, STANAG 1008 | |
| For more information and support, please feel free to contact us | |
No matching FAQs found.
A three phase Static Frequency Converter is used to convert electrical power from one voltage and frequency to another, typically from 230V 50Hz to 115V 60Hz, 60Hz to 50Hz and to 400Hz. This allows industrial machinery, motors, pumps, compressors and other three phase equipment to be powered from the appropriate supply voltage and frequency.
Yes. The PX Electronics three phase Static Frequency Converters can be configured for 50Hz to 60Hz, 60Hz to 50Hz or 50/60Hz to 400Hz.
Yes. The SFC system can be configured for 60Hz to 50Hz conversion. This is useful when operating European or UK equipment in regions where the available AC power supply is 60Hz.
Yes. Three phase Static Frequency Converters are commonly used with industrial machinery, production equipment, motors, pumps, compressors, HVAC systems and specialist electrical loads. The final system rating should be selected based on the load type, inrush/starting current and duty cycle.
Key information includes the available input supply voltage and frequency, output voltage and frequency, load power rating kVA, load type, starting or inrush current, indoor/outdoor operating environment and any control or communication requirements like RS485.
Yes. PX Electronics can provide configurations to suit different voltage, frequency, power rating, enclosure types, control and monitoring requirements. This is particularly useful for industrial, marine and export testing applications where standard supply conditions or environment do not match those of the connected equipment.
Yes, a three phase Static Frequency Converter (SFC) can convert to single phase AC supply.
Yes. The PXe-C Series can be configured for commercial as well as industrial applications where three-phase voltage or frequency conversion is required. Typical examples include imported equipment, building services, test facilities, commercial machinery and equipment designed for a different regional mains supply. The input supply, output voltage, frequency and connected load are reviewed when the converter is specified.
Yes, three phase static frequency converters (3ph SFC) are often used in marine and shore power applications where vessel or dockside equipment requires a different supply frequency. Typical ship shore power operates at 60 Hz. However, because most local shoreside grids (such as those in the UK and Europe) operate at 50 Hz, ports often require SFC to match the vessel's frequency and voltage.
Yes. Manufacturers can use a PXe-330000-C 50Hz to 60Hz or 60Hz to 50Hz static frequency converter to test equipment under the same operating electrical conditions as the destination country. This is useful for testing, validation, factory acceptance testing and production quality checks.
Yes. The PXe-C Series can be configured for a 240/120V three-phase, four-wire High-Leg Delta output where required by the connected equipment or installation.
This arrangement provides 240V phase-to-phase, 120V from two phases to neutral, and approximately 208V from the high leg to neutral. The high leg is not used for 120V line-to-neutral loads.
The required transformer winding, neutral arrangement, phase designation and expected line-to-neutral loading should be confirmed when the SFC is specified.
A Static Frequency Converter uses solid-state power electronics and is much lighter and more compact than rotating machinery. The SFC allows more control of output voltage and frequency, along with precise control of its V and A protection. Unlike rotary machines, there are no mechanical maintenance requirements
Static Frequency Converter (SFC) fault diagnostic systems work by monitoring voltage, current, power, and phase loss. These errors are written to Non-Volatile RAM (NVRAM) for later viewing. SIL Watch-dog options are available for independent monitoring and reporting.
Watch-dog, or independent fault monitoring systems, are available for monitoring and reporting the health of Static Frequency Converters, in particular high kVA units. This autonomous fault diagnostic systems works by monitoring voltage, current and power and phase loss. These errors are written to Non-Volatile RAM (NVRAM) and can be sent via Networks and SMS.